The microclimate control system is designed to control the air conditioner and heaters in order to maintain normalized microclimate parameters in the driver's cab of an electric locomotive (according to safety standards for railway transport 04-98), both in automatic mode (see table below) and when the temperature is individually set within + 18...28°С.
Cabin air temperature, °С
- at outside air temperature from minus 50 to plus 20°С - 22±2
- at outside air temperature from plus 20°С to plus 40°С - 22+0,25 (t outer -19)
- at outside air temperature above plus 40 °С - not more than 28
The specified temperature is maintained with an accuracy of ±2 °С.
The climate control system consists:
Name | Quantity, pcs | Overall dimensions, mm | ||
L | B | H | ||
The operating and display unit | 1 | 40 | 150 | 150 |
The control and switching unit | 1 | 300 | 210 | 500 |
Temperature sensor | 3 | 40 | ø12 | |
Humidity sensor | 1 | 40 | ø12 |
Air conditioner power supply - network 380 V, 50 Hz, heaters - network 220 V, 50 Hz;
Power consumption, kW, not more:
- in air conditioning systems - 3,5.
- heaters, 2 pcs. - 7,0.
- blocks of flat electric heaters, 3 groups - 4,5.
- electric convection ovens, 4 pcs. - 3,2 kW.
- air heaters of the heat curtain, 2 pcs. - 0,8 kW.
Control circuits power supply:
- the network of the constant voltage 24 V or network 220 V
- power consumption not more than 30 W
- Climatic version U, location category 2 with operating temperature range from -50 °С to 55 °С
- Mechanical design: group М25 according to GOST 17516.1